Wire size calculator
A 16 A load at the end of a 100 ft, 120 V single-phase copper run needs 10 AWG to stay inside a 3% allowance - 12 AWG would carry the current but drops too much over that distance. At 10 AWG the drop is 3.2 V, or 2.7% of 120 V.
Result
- Size to use
- 10 AWG
- Cross-section the drop limit demands
- 4.67 mm²
- Voltage drop
- 3.2 V
- Drop as a percentage
- 2.7 %
- Allowance left unused
- 0.3 %
- Ampacity of that size
- 30 A
NEC Table 310.16, copper, 60 °C (140 °F) column - Copper conductors, not more than three current-carrying conductors in a raceway or cable, 30 °C (86 °F) ambient, 60 °C termination rating. Higher ambient temperatures, more conductors in the same raceway, or conductors in sunlight on a rooftop all reduce these figures. The 60 °C column is used here because it is the column 240.4(D) leaves you with on 14, 12 and 10 AWG anyway, and because most 15 A and 20 A devices are only listed for 60 °C terminations.
One size either way, for this run
- 12 AWG4.2 % · 5.1 VOver the allowance
- 10 AWG2.7 % · 3.2 VWithin the allowanceyour cable
- 8 AWG1.7 % · 2.0 VWithin the allowance
Permitted drop: 3.0 % · ASTM B258
How the calculation works
Sizing a conductor is two separate questions, and the calculator above answers the one that tables do not. Ampacity asks whether the wire can carry the current without overheating; that comes from NEC Table 310.16 with its correction and adjustment factors. Voltage drop asks whether enough voltage survives the trip to the load, and that is pure arithmetic:
A ≥ k · ρ(T) · L · I / ΔU
A is the cross-section in mm², k is 2 for DC and single phase (current goes out
and comes back) or √3 for three phase, ρ(T) is the resistivity of the metal at its
working temperature, L is the one-way length, I the load current, and ΔU the
volts you are willing to lose. Copper at 20 °C is 0.017241 Ω·mm²/m; the calculator
corrects it with α = 0.00393 per K when you raise the temperature.
The result is then rounded up to the next size that actually exists - AWG sizes come from the ASTM B258 definition rather than a typed-in table, so they cannot drift. Rounding down would hand you a wire that misses the allowance you just typed in, which is why the figure you buy is always at least the figure the formula asks for.
What the calculator will not do is invent an ampacity for a size. Current-carrying capacity depends on the table, the termination rating, the ambient temperature and how many conductors share the raceway - so the US edition consults the 60 °C copper column of Table 310.16 and says so, and nothing is implied about installation methods it cannot see.
Worked example
Your circuit
- System
- Single phase AC
- Supply voltage (V)
- 120.0 V
- Load current (A)
- 16 A
- Run length, one way
- 100 ft (30.5 m)
- Conductor material
- Copper
- Size series
- AWG
- Voltage drop allowed (%)
- 3.0 %
Result
- Cross-section the drop limit demands
- 4.67 mm²
- Size to use
- 10 AWG
- Voltage drop
- 3.2 V
- Drop as a percentage
- 2.7 %
- Allowance left unused
- 0.3 %
- Ampacity of that size
- 30 A
- Formula
A ≥ k · ρ(T) · L · I / ΔU- Standard
- ASTM B258 (AWG), IEC 60028
- Limits of the model
- The resistive model is used: conductor reactance is not included, which is negligible below roughly 95 mm² and on the short runs this tool is for.
Computed by Voltacalc with the same engine as the tool above.
What applies in the United States
The 60 °C column of NEC Table 310.16 and the small-conductor rule in 240.4(D) set what the breaker may be - 15 A on 14 AWG, 20 A on 12 AWG, 30 A on 10 AWG - and no amount of upsizing for voltage drop changes those limits. Upsizing the wire for a long run is normal practice and does not entitle you to a bigger breaker, because the breaker still protects the smallest conductor in the circuit.
- Who decides
- NFPA / the authority having jurisdiction (AHJ) in your state or city
- Standard
- NEC (NFPA 70), National Electrical Code
- Ampacity table
- NEC Table 310.16, with the correction and adjustment factors of 310.15(B) and (C), and the small-conductor rule in 240.4(D)
- Permitted drop
- The NEC does not make voltage drop a rule for most branch circuits: 210.19(A) and 215.2(A)(1) carry Informational Notes recommending no more than 3% on the branch circuit and 5% for feeder plus branch combined. Your AHJ, or a specific article such as 647.4(D), can make a lower figure mandatory. (Checked: September 12, 2026)
Questions electricians ask
Does the calculator use one-way or round-trip length?
One way. Enter the distance from the panel to the load and the calculator doubles it for you, because on a 120 V or 240 V circuit the current travels out on one conductor and back on another.
Why does it give me a bigger wire than the ampacity table?
Because it sizes for voltage drop, not heat. Ampacity answers "will this wire survive the current"; voltage drop answers "will the load still see enough volts". On long 120 V runs the second question almost always asks for more copper than the first.
Is 3% a code requirement?
No. The NEC carries 3% on the branch circuit and 5% total as Informational Notes - recommendations, not rules - although your AHJ or a specific article such as 647.4(D) can make a tighter figure mandatory.
Can I use aluminum instead?
Yes, and the calculator has it as an option, but aluminum's resistivity is about 64% higher than copper's, so the same drop allowance needs roughly two gauge sizes more. Terminations have to be listed for aluminum too.
Standards and sources
- NEC (NFPA 70), National Electrical Code
- NEC Table 310.16, with the correction and adjustment factors of 310.15(B) and (C), and the small-conductor rule in 240.4(D)
Last updated: September 12, 2026
Calculators
- Voltage dropVolts lost, percentage and voltage left at the load for a cable you already have.
- Ohm's lawAny two of V, I, R and P in; the other two out, with the stock values that come closest.
- Amps, watts and voltsNameplate to current and back, with power factor, efficiency and the breaker check.
- Resistor color codeBands in, ohms out - plus the range the tolerance band really allows and the reading a misread ring would give.
- Breaker sizeThe standard rating above your design current - and whether the cable behind it can carry that rating at all.